WATER STORAGE
Sectional Tank Components
3D Sectional Tank Training
Our 3D interactive sectional tank and AR function will help you upskill and discover the complete range of components tank components and why they are used. Access the Web AR on the right hand side of the 3D model to virtually display it in your plantroom.
Interact with our 3D sectional GRP tank animation and VR tool! Upskill today and discover a complete range of tank components and why they are used. Virtually display the sectional tank within a room, or watch our interactive AR video below for more information!
If you have any questions, feel free to call us or use our quote form
To speak to one of our agents online, click here
Overview of Each Sectional Tank Component
Inlet Connection
This where water enters the tank.
There can be various types of inlet connections, i.e. Equilibrium Float Valve, Keraflo Float Valve, Tank Connection Only (with water flow controlled by level switches) or other control units such as TankTronic modules
Outlet Connection
This is where the water exits the tank.
Overflow Connection
The actual internal diameter of the pipe(s) installed should be capable of taking any possible flow in the pipe arising from any failure of the inlet valve.
Recommended that the overflow is 2x the inlet pipe diameter.
See Water Regulations 1999 sections 7.8 to 7.11 for further guidance.
Warning Pipe
The purpose of the warning pipe is merely to alert people to a fault and to an impending overflow.
Required on tanks with an actual capacity of 1000 litres or greater.
See Water Regulations 1999 sections 7.8 to 7.11 for further guidance.
Lid Support
A Lid support is designed to support lids on tanks that span over 1m in width and length.
Raised Inlet Valve Housing
Enables the inlet connection for the tank to be fitted at a higher level.
This could be due to the requirement for increased actual capacity, or ease of installing certain air gap requirements such as an AB air gap type.
External Ladder
Recommended where the height of the tank is greater than 1.5m.
Guardrail
Edge Protection designed to be fixed to the top of the tank to prevent the fall of any person who has to climb on top for maintenance purposes.
This has to be risk assessed by the site/designer/end user as a requirement if deemed necessary.
Access Manway
Standard Hinged or “lift off” options this will depend on the configuration of the tank.
Internal Ladder
Recommended where the height of the tank is 1.5m or greater.
Recommended for ease of access during maintenance/inspection.
Internal Tie Rods
S/S 316 Grade A4 internal ties brace the tank from outward water pressure.
On tanks, 1.5m high and greater, with a footprint of 1.5×1.0m and greater.
Stayplate
External bracing support for internal tie bars.
Required on certain tanks of 2.5m high and greater.
Drain Connection
A dedicated connection for draining contents of tank during maintenance/inspection.
Temperature Dial or Sensor
Available as either a visual dial readout or sensor to report back to BMS system.
Level Switch
High and/or Low. An electromechanical device that opens or closes a digital switch when the fluid in a given area reaches a certain level.
Commonly used to protect/control pump sets when low level is reached, or as an alarm warning when a high level is reached.
1x1m GRP Tank Panel
Hot Press Moulded 1m x 1m truncated tank panel, insulated as standard. Can be provided as an uninsulated option.
Where connections are being fitted to a tank that particular panel will be changed to a flat panel to accommodate.
1×0.5m GRP Tank Panel
Hot Press Moulded 1m x 0.5m tank panel, insulated as standard. Can also be provided as an uninsulated option.
0.5×0.5m GRP Tank Panel
Hot Press Moulded 0.5m x 0.5m tank panel, insulated as standard, but can be provided as an uninsulated option.
Primary Supports
For Externally Flanged Base tank, normally set @ 1000mm centres @ 600mm high.
Secondary Support
Steel used to cross Primary Supports where Externally Flanged Base tank is required to be supported @ 500mm centres, normally on Externally Flanged Base tanks of 2.5m high and greater.
Or where footprint configuration of the tank may cause access issues I.e. if there were a 0.5m increment on length/width two primary supports may end up too close together for safe access underneath.
Internal Maintenance Division
Construction of one or more panels within a tank which divides the tank into two separate compartments.
Note: In any situation where there is only one water storage tank in a building, it is to be recommend that a weir or a division plate be used. This will facilitate maintenance of the tank without affecting the water supply to the building.
AB Air Gap Spill Slot
Cat 5 Tanks, also known as Type AB Airgap Break Tanks (Category 5 Backflow Prevention)
Category 5 risks are fluids that pose a serious health risk due to the concentration of pathogenic organisms or extremely toxic or radioactive elements present with them including any fluid which contains; faecal material or other human waste: butchery or other animal waste: or pathogens from any other source.
Water Supply (Water Fittings) Regulations 1999 in England and Wales and Scottish Water Byelaws state the installation of cold water storage tanks, connected to the public water supply must comply with the UK water fitting regulations. In order to meet these requirements, Category 5 Break Tanks must be used.
Vent
Opening to the atmosphere to allow for the movement of air resulting from changes in the water level so that the water always remains at atmospheric pressure.
Sparge Pipe
A device used to achieve optimum circulation of water stored within a tank or cistern.
Its application is generally reserved for installations where space around a tank is restricted. Reasonable access to the tank side directly opposite the Mains Inlet is not available.
Watch Our Video - How to use Our AR Tool
Technical Data Brochure
Download our detailed technical data brochure
online form
Arrange a callback or email enquiry
Recent Projects
Extensive industry experience, manufacturing since 1973.
Tricel manufacture deliver & install cold water storage tanks across a wide range of industry sectors throughout Ireland & the UK. Tricel also provide an import/export services for our international clients. Tricel have been Manufacturing water tanks since 1973, and are made from Glass Reinforced Plastics (GRP). This top quality material offers outstanding capabilities including long life, durability and is a cost effective solution for water storage even in the harshest environments. Cold water storage is available for both potable and non-potable applications.