GRP Cold Water Storage Tanks - UK Manufacturer Est. 1956

GRP Sectional Category 5 Break Tanks

Tricel manufactures hot-press moulded GRP sectional tanks with a Type AB air gap – a raised inlet valve housing with an AB air gap spill slot (weir overflow) – for mains connections serving a fluid category 5 risk. Site-assembled from modular panels, from 1,000 to over 4 million litres, for plant rooms where a one-piece Cat 5 tank cannot be delivered or is too small.

  • •Type AB air gap – rated by the Regulators for fluid category 5, the highest risk level
  • •Non-mechanical: a permanent physical air gap, with no check valves in the protection path
  • •EFB, IFB and TIF configurations – Cat 5 suitability confirmed at enquiry stage
  • •Regulation 4(1)a approved sectional tanks; WRAS-approved fittings where specified
  • •Assembled on site by Tricel-trained installation teams across the UK

Cat 5 Sectional Break Tank – Key Parameters

Air gap type

Type AB (raised housing + spill slot)

Fluid category

Category 5 - highest risk

Capacity range

1,000 L – 4M+ litres

Configurations

EFB / IFB / TIF

Panel construction

Hot-press moulded GRP

Approval

Regulation 4(1)a / WRAS fittings

Regulations

WSFR 1999 / Scotland Byelaws 2014 / NI 2009

Manufacturer

Tricel Water UK - UK manufacturer

What is a Category 5 sectional break tank?

A Category 5 sectional break tank is a GRP sectional cold water storage tank, assembled on site from hot-press moulded panels, fitted with a Type AB air gap so that it can be connected to the mains where the downstream system presents a fluid category 5 risk under the Water Supply (Water Fittings) Regulations 1999. The mains inlet sits in a raised inlet valve housing, and an AB air gap spill slot (a rectangular weir overflow) sets the critical water level. The air gap between the lowest point of the inlet and that critical level must be at least 20 mm or twice the inlet bore, whichever is greater. Because there is no physical connection between the inlet and the stored water, backflow into the public supply cannot occur by back-siphonage or back pressure. Tricel manufactures GRP sectional tanks in EFB, IFB and TIF configurations from 1,000 to over 4 million litres; the sectional format suits Cat 5 installations that need larger capacity, restricted-access delivery or like-for-like replacement in an existing plant room.

01

Fluid Categories

Understanding Fluid Categories and Why Category 5 Requires an Air Gap

The Water Supply (Water Fittings) Regulations 1999 classify contamination risk into five fluid categories. The category of the downstream system determines the minimum backflow protection on the mains connection. At category 5 only a non-mechanical air gap rated for that category – such as Type AA or Type AB – is acceptable. A Type AG air gap is rated for fluid category 3 at most.

Category
Risk level
Fluid description
Examples of protection rated for this category
1
No risk
Wholesome water supplied by a water undertaker
None required
2
Aesthetic
Water that would be wholesome but for a change in temperature, taste, odour or appearance
Single check valve, or any device rated for a higher category
3
Slight health hazard
Fluid containing substances of low toxicity
Type AG air gap; double check valve
4
Significant health hazard
Fluid containing toxic, carcinogenic or pesticide substances
Type BA (RPZ) valve; Type AF air gap
5
Serious health hazard
Fluid containing pathogenic organisms, radioactive or very toxic substances, or faecal, human or animal waste
Non-mechanical air gap only – e.g. Type AA or Type AB. No mechanical device is acceptable.

The fluid category is set by the risk of the downstream system, not the water stored in the tank. The water undertaker or a competent person must assess and confirm the category for each installation. Full device ratings are set out in the Regulators’ Specification for backflow prevention arrangements and devices.

02

The AB Air Gap

How a Type AB Air Gap Works on a GRP Sectional Tank

On a Tricel sectional tank, the Type AB air gap is formed by a raised inlet valve housing and an AB air gap spill slot. The arrangement is designed for each tank configuration and confirmed at design stage.

Raised inlet valve housing – The inlet connection and float valve are mounted in a housing raised above the main tank lid, so the point of discharge sits well above the stored water.

AB air gap spill slot – A rectangular weir overflow sets the critical water level – the level reached under fault conditions, measured two seconds after the inlet is closed. If the float valve fails, water discharges through the slot before it can rise to the inlet.

Measured air gap – The vertical gap between the lowest point of the inlet and the critical water level must be no less than 20 mm or twice the inlet bore, whichever is greater. It can be confirmed by test or calculation.

Unrestricted discharge – Neither the water path to the spill slot nor the discharge from it may be restricted, so the space outside the slot must allow full, unimpeded discharge.

No mechanical parts in the protection path – Unlike RPZ or check valves, an air gap has no seals or moving parts that can fail. Protection is maintained by the physical gap itself.

Modifying the inlet housing, spill slot position or inlet arrangement after installation may compromise the air gap. If the inlet comes into contact with the tank contents – for example through splashing or foaming – the air gap is considered compromised. Confirm any changes with Tricel.

03

Why Sectional

Why Specify a Sectional Cat 5 Break Tank?

Tricel also manufactures one-piece Category 5 break tanks. A sectional tank is the alternative where access, capacity or the plant room layout rule out a complete moulded unit.

01

Restricted-access plant rooms

Panels are delivered individually and bolted together on site, so the tank can be installed via stairwells, narrow corridors and goods lifts where a one-piece Cat 5 tank cannot be positioned.

02

Capacity beyond the one-piece range

Sectional tanks run from 1,000 to over 4 million litres. Capacity is set by footprint and headroom, not a fixed product size – one-piece tanks are supplied in fixed sizes up to 16,000 litres.

03

Replacement of existing tanks

An existing tank can be dismantled panel by panel and a new Cat 5 sectional tank assembled in the same space, including where perimeter clearance is limited (TIF).

04

Configurable to the project

Inlet position, raised housing, connections, access hatch and base type are designed per project, with standard 1m panels plus half-panel increments.

05

Maintenance without losing supply

An internal maintenance division can split the tank into two compartments so one can be isolated for cleaning or inspection while the other continues to supply the building.

06

Made by the manufacturer

Panels are hot-press moulded in-house at Weston-super-Mare and Lanark and assembled by Tricel-trained crews – no distributor between design and installation.

04

Tank Types

EFB, IFB and TIF Cat 5 Sectional Tank Configurations

All three sectional configurations use hot-press moulded GRP panels. The right type depends on headroom, perimeter clearance, access route and pipework position. Cat 5 AB air gap suitability is confirmed for each configuration at enquiry stage.

Tank type
Best for
Key advantage
Cat 5 consideration
EFB – External Flanged Base
Open-access sites with standard perimeter clearance and headroom
Raised self-draining base; access below the tank for cleaning and maintenance
Allow for the overall height of the base frame plus the raised inlet valve housing
IFB – Internal Flanged Base
Sites where headroom is limited
Lower installation height than EFB; flat base or levelled steel beams
Raised housing still adds height above the lid – check hatch and housing clearance
TIF – Totally Internally Flanged
Constrained plant rooms and retrofit
Assembled from inside; ~50 mm clearance achievable on three sides
~500 mm on the pipework side; spill slot discharge must remain unrestricted

05

Applications

Where Category 5 Sectional Break Tanks Are Specified

Category 5 protection is needed wherever a mains connection serves a system with a fluid category 5 risk. Typical sources include laboratories, mortuaries, veterinary practices, clinical areas in hospitals, agricultural livestock systems and bin stores. The sectional format is commonly chosen in these sectors where storage volumes are large or plant rooms are constrained.

Healthcare & NHS

Hospitality & Leisure

Infrastructure & Utilities

Data Centres

High-Rise & Multi-Storey

Industrial & Manufacturing

Education

Agriculture

Food & Beverage

Local Authority & Public

The required fluid category for any specific installation must be confirmed by the water undertaker or a competent person registered under an Approved Contractor Scheme. Do not determine fluid category without a formal assessment.

This list is indicative only. Whether a Cat 5 risk exists depends on the activities and water uses at each installation, and must be assessed by the water undertaker or a competent person.

06

Specification

Tricel GRP Sectional Cat 5 Break Tank – Specification

Parameter
Specification
Tank construction
Site-assembled GRP sectional tank – hot-press moulded panels (isophthalic polyester resin, glass fibre reinforcement)
Panel sizes
1m × 1m standard; 1m × 0.5m and 0.5m × 0.5m panels for half-panel increments
Capacity
1,000 L to over 4 million litres – confirmed per project footprint and headroom
Configurations
EFB, IFB, TIF – Cat 5 suitability confirmed at enquiry stage
Air gap type
Type AB – raised inlet valve housing with AB air gap spill slot (weir overflow)
Fluid category protection
Category 5 (back-siphonage and back pressure)
Air gap dimension
≥ 20 mm or 2 × inlet bore (whichever is greater), to the critical water level
Approval
Regulation 4(1)a approved sectional tanks; WRAS-approved fittings available where specified – confirm requirements at quotation
GRP reference standard
BS EN 13280:2001 – GRP cold water storage tanks
Backflow reference
BS EN 1717; Regulators’ Specification for backflow prevention
Insulation
Insulated and uninsulated panel options – specify to suit location and use
Float valve sizing
Confirmed to incoming mains supply at order
Options
Internal maintenance division, internal/external ladders, access manway, level switches, temperature sensor, drain connection
Manufacturer
Tricel Water UK – Weston-super-Mare and Lanark

07

AG vs AB Air Gap

AG Air Gap vs AB Air Gap: What Is the Difference?

Both are non-mechanical air gaps with the same minimum gap dimension. The difference is the overflow: AG uses a minimum-size circular overflow and is rated up to fluid category 3; AB uses an unrestricted rectangular weir and is rated for category 5.

Feature
Type AG Air Gap
Type AB Air Gap (Cat 5)
Fluid category rating
Up to category 3
Up to category 5 (highest)
Overflow type
Circular, minimum 19 mm bore throughout
Rectangular weir / spill slot, unrestricted
Minimum air gap
20 mm or 2 × bore, whichever is greater
20 mm or 2 × bore, whichever is greater
Protects against
Back-siphonage and back pressure
Back-siphonage and back pressure
Inspection interval (BS EN 806-5)
Every 12 months
Every 6 months, including screened mesh
Tricel sectional range
Standard sectional tank inlet arrangements
Raised inlet valve housing + AB air gap spill slot

08

Sectional vs One-Piece

Sectional vs One-Piece Category 5 Break Tanks

Requirement
Sectional Cat 5 break tank
One-piece Cat 5 break tank
Construction
Hot-press moulded panels assembled on site
Single moulded GRP unit, delivered complete
Capacity
1,000 L to over 4 million litres
Fixed sizes within the one-piece range (up to 16,000 L)
Restricted access
Strong option – panels moved through stairwells, corridors and lifts
Needs a clear route for the complete tank
AB air gap
Raised inlet valve housing and spill slot designed per project
Factory-fitted raised housing and weir; WRAS-approved assembly
Programme
On-site assembly time depends on tank size
Shortest on-site programme
Best for
Large volumes, plant room replacements, constrained sites
Smaller volumes with clear delivery access

09

Regulations

Regulations Governing Category 5 Break Tanks

Compliance is determined by the complete system specification – tank, fittings, pipework, overflow arrangement, insulation, access and maintenance – not by the tank alone.

Jurisdiction

UK water fittings legislation

England & Wales: Water Supply (Water Fittings) Regulations 1999. Scotland: Water Supply (Water Fittings) (Scotland) Byelaws 2014. Northern Ireland: Water Supply (Water Fittings) Regulations (Northern Ireland) 2009.

Regulation 4

Fittings of appropriate quality

Water fittings must be of appropriate quality and standard. Tricel sectional tanks are Regulation 4(1)a approved for potable cold water storage where specified.

Regulation 5

Prior notification

Installing a backflow prevention arrangement for a fluid category 4 or 5 risk requires notice to the water undertaker before work starts. Consent is deemed if not refused within 10 working days. Approved contractors may be exempt – check with the scheme.

Schedule 2, para 15

Backflow prevention

Every water system must contain adequate devices to prevent backflow. Device ratings by fluid category are set out in the Regulators’ Specification.

BS EN 1717

Protection against pollution

The British adoption of the European standard on protection of potable water against pollution by backflow, classifying devices by fluid category.

ACoP L8 · HSG274

Legionella control

Stored cold water should be kept below 20°C. Insulation, correct sizing and adequate turnover support Legionella risk management.

Contravening the Water Fittings Regulations or Byelaws is a criminal offence and can lead to enforcement by the water undertaker. Always confirm requirements with the water undertaker before installation.

10

Installation

Installation and Clearance for Cat 5 Sectional Tanks

The clearance guidance for standard sectional tanks applies, plus allowances for the raised inlet housing and the spill slot discharge.

Clearance / requirement
Indicative guidance
Notes
Perimeter – tanks up to 2m high
500 mm
All sides, for inspection, cleaning and maintenance
Perimeter – 2.5–3m high
800 mm
Increased clearance for working at height
Perimeter – 3.5–4m high
1,000 mm
Confirm at design stage
TIF – pipework side / other sides
~500 mm / ~50 mm
Subject to design confirmation
IFB hatch clearance
750 mm hinged / 500 mm lift-off
Above the hatch opening
Raised inlet valve housing
Project-specific
Headroom must include the housing height above the tank lid
AB spill slot discharge
Unrestricted
Leave enough space outside the slot for full discharge under fault conditions
Overflow and warning pipe
≥ 1.5 × max inlet flow
Route to a visible, traceable discharge point
Base flatness tolerance
2 mm per 1 m / 6 mm per 6 m
Panel alignment and joint seal integrity

01

Before installation

  • Fluid category confirmed by the water undertaker or a competent person
  • Regulation 5 notice submitted where required
  • Approval and fittings documentation agreed for the project

02

On site

  • Access route checked for panel delivery
  • Flat, level, load-bearing base
  • Assembly by Tricel-trained crews

03

Commissioning

  • Air gap verified against the critical water level
  • Clean, disinfect and flush to BS 8558:2015
  • Retain notification, approval and commissioning records

These are indicative design guidance values, not universal regulatory requirements. Confirm against the tank type, configuration and current Tricel installation guidelines.

11

Aftercare

Cat 5 Break Tank Aftercare and Inspection

Tricel Water UK has partnered with Hydraclean Ltd, a water hygiene and Legionella compliance specialist, to deliver aftercare compliant with ACoP L8, HSG274 and BS 8558:2015.

BS EN 806-5

AB air gap inspection

Type AB air gap installations, including screened mesh, should be inspected, cleaned and maintained as necessary every 6 months.

HSG274 · ACoP L8

Tank inspection

Best practice every six months; annual minimum. Checks include stored water below 20°C, screens, sediment and stagnation risk.

BS 8558:2015

Cleaning & chlorination

Risk-assessed cleaning and disinfection, with confined-space protocols and photographic records. UKAS-accredited sampling where required.

12

Technical Downloads

Cat 5 Sectional Break Tank Technical Resources

Technical documents for M&E engineers, specifiers, building services consultants and facilities managers. Download for design, specification, procurement and regulatory submissions.

GRP Sectional Tank Product Brochure

EFB, IFB and TIF configurations, capacities, approvals and panel sizes.

TIF Tank Technical Brochure

Totally internally flanged tanks for constrained plant rooms.

IFB Tank Technical Brochure

Internally flanged base tanks – design and application.

Backflow Prevention Guide

Fluid categories, air gap types and device selection.

Break Tank & Booster Set Design Guide

Sizing, two-compartment arrangements and booster set interface.

Tank Aftercare Brochure

Tank aftercare servicing packages and recommended timelines.

13

Specification Support

Specify a Tricel GRP Sectional Cat 5 Break Tank

Information for a quotation

Fluid category confirmed (water undertaker)

Required storage capacity (litres)

Internal or external location

Available footprint and headroom (incl. raised housing)

Access route constraints

Preferred tank type, if known

Incoming mains diameter (float valve size)

Potable or non-potable duty

Insulated or uninsulated

Maintenance division required?

Regulation 5 notification status

Plant room drawings / existing tank details

Send project details to Tricel

Tricel’s technical sales team will review your requirements and advise on tank type, panel layout, AB air gap arrangement, base type and access strategy.

15

FAQS

Category 5 Sectional Break Tank FAQs

Common questions from consulting engineers, M&E contractors and specifiers.

What is a Category 5 sectional break tank?

A GRP sectional cold water storage tank, assembled on site from hot-press moulded panels, fitted with a Type AB air gap – a raised inlet valve housing with an AB air gap spill slot. It provides backflow protection for mains connections serving a fluid category 5 risk under the Water Supply (Water Fittings) Regulations 1999. Tricel manufactures sectional tanks from 1,000 to over 4 million litres.

Choose sectional where the complete tank cannot be delivered to the plant room, where the required volume exceeds the one-piece range (fixed sizes up to 16,000 litres), or where an existing tank is being replaced in a constrained space. One-piece Cat 5 tanks offer the shortest on-site programme where access allows.

Tricel’s GRP sectional tanks and TIF configurations can be specified to meet fluid category 5 requirements. Suitability of the AB air gap arrangement for each configuration is confirmed at enquiry stage, taking account of headroom, inlet position and spill slot discharge clearance.

Both need an air gap of at least 20 mm or twice the inlet bore. A Type AG air gap uses a minimum-size circular overflow and is rated up to fluid category 3. A Type AB air gap uses an unrestricted rectangular weir overflow and is rated up to fluid category 5.

Under Regulation 5, installing a backflow prevention arrangement for a fluid category 4 or 5 risk requires notice to the water undertaker before work begins. Consent is deemed if not refused within 10 working days. Work by an approved contractor may be exempt – confirm with the relevant scheme.

BS EN 806-5 recommends Type AB air gap installations, including screened mesh, are inspected and maintained every 6 months. HSG274 recommends cold water storage tank inspection every six months as best practice, and at least annually.

Tricel sectional tanks are Regulation 4(1)a approved for potable cold water storage where specified. Potable compliance depends on the full specification – fittings, insulation, access and maintenance – and stored water should stay below 20°C. State potable duty at quotation stage.

The confirmed fluid category, required capacity, location, footprint and headroom (including the raised housing), access route, mains diameter, potable or non-potable duty, insulation and any drawings. Contact +44 (0)1934 421 499 or websales@tricelwater.co.uk.

Tricel Water UK - UK GRP Tank Manufacturer

Need a Category 5 sectional break tank for your project?

Send the confirmed fluid category, required capacity and plant room constraints. Tricel will advise on configuration, AB air gap arrangement and documentation.